更新時間:2021-07-22點擊次數(shù):1027次
Application of open type Hall current sensor in power distribution system modification in a Russian

Abstract: According to the principle, characteristics and installation mode of the open-type Hall current sensor, the application of the open-type Hall current sensor in the transformation and distribution system of the factory is analyzed, so as to provide a solution for users to realize the intelligent distribution of DC system quickly.


Key words: open type Hall current sensor  DC distribution system  working principle  application

 

0 Overview

  DC distribution system is usually composed of high frequency switching power supply and battery, which is used to provide reliable DC power supply for control, signal, relay protection and automatic devices, accident lighting and so on in DC system. It has high requirements for the reliability, stability and quality of power supply. Therefore, in the Russian DC system, we matched the DC Hall distribution meter used. During the transformation of DC system, there is no power outage, and the engineering transformation is difficult, and the traditional closed Hall current sensor or shunt can not solve the problem. Therefore, the open Hall current sensor can be used to solve the DC current measurement problem in the transformation project, so as to ensure the safe operation of the transformation process without power outage.


1 Product Design   

1.1Structural features     

  Open-mouth Hall current sensor is developed on the basis of traditional closed-mouth Hall current sensor. It has novel structure and beautiful appearance. The whole is composed of shell, iron core, sampling circuit board and fixed resin. The shell material is made of PC/ABS alloy, which has the characteristics of high temperature resistance, high mechanical strength and environmental protection. The core is made of oriented cold bonded silicon steel sheet, which has the characteristics of stable performance, high mechanical strength and extremely high magnetic conductivity. Green pluggable terminal is used for circuit board and external wiring, which is convenient and reliable for on-site wiring. The specific structure is shown in Figure 1 and 2. The appearance of the product adopts split design. Figure 1 is a round pass, which is suitable for passing through the DC system when the primary bus is a cable. , Fig. 2 square pass, suitable for the DC system when the primary bus is copper bar. According to the measurement range of primary current and perforation requirements, the corresponding product type can be selected. This series of sensors can measure the current range of 20A ~ 20000A, the main shape of the phi 20, 40, 60, 64*16, 85*27, 104*36, 140*50 and other specifications, as shown in Figure 3, suitable for different applications.

        

                Fig. 1 circular pass pattern                            Fig. 2 Square pass pattern                           


       Figure 3 AHKC series open type Hall current sensor


1.2 Working principle

  Hall current sensor based on hall effect, electromagnetic induction principle, design of a sensor, according to the principle can be divided into the open loop mode (straight) and closed loop mode (magnetic balance type), open hall current sensor is in a traditional open loop (straight) is improved on the basis of hall sensor, is different from traditional single core, single chip design hall, In order to design a split structure, the iron core is separated and installed symmetrically. The hardware adopts parallel complementary differential input of double Hall chips. The principle of open-type Hall sensor is shown in Figure 4:

                       Fig. 4 Schematic diagram of open Hall sensor


  When the primary side current IP flows through a long wire, will produce a magnetic field around the wire, the size of the magnetic field and is proportional to the current through the wire, the magnetic field gathered in the circular, through two hall element in the circular air gap measurement, two hall element marks instead placed in the same field, the output signal with complementary characteristics of output voltage by differential amplifier output, Not only can suppress the common mode interference, but also the influence of temperature drift, the output voltage VS accurately reflect the original side current IP. The general rated output is calibrated as DC±5V or DC4-20mA.


1.3 Product installation

  Take square-hole products as an example, as shown in Figure 5, open the mounting screw of the open-type Hall current sensor, and remove the lower body of the sensor; The upper body of the open type Hall current sensor is loaded into the primary bus of the distribution system, and the lower body of the sensor is closed. The mounting screws and gaskets of the sensor pass through the fixing holes of the upper and lower bodies, and the upper and lower bodies of the sensor are fixed together. If on-site power off installation is possible, two corresponding threaded holes can be opened on the bronze plate according to the sensor spacing requirements, and the sensor is fixed on the threaded hole of the bus bar through the rear mounting fixing hole to complete the installation of the sensor; If the site requires continuous electric installation, the supporting rubber pad can be embedded between the shell and the bronze plate to ensure that the sensor can work reliably under vibration conditions. The whole installation process is relatively quick and simple. 

Fig. 5 Product installation diagram


1.4 Advantages of open type Hall sensor

  Compared with the traditional DC current measurement method generally adopted by shunt or transformer, the open-type Hall sensor has the following advantages:

1) High insulation strength of primary side and secondary side, up to AC 12KV isolation;

2) No insertion loss;

3) Good dynamic performance: the response time is less than 20uS and the tracking speed Di /dt is higher than 20A/ uS

4) There is no need to disassemble the original side cable or bus during installation. It is especially suitable for the transformation and construction of equipment that is not allowed to lose power.


2. Product application

   Open-end Hall current sensor is mainly used in the transformation of DC distribution system in factories, such as DC power system transformation in power plants, DC system transformation in substations, communication room transformation, railway locomotive transformation and other projects. It can convert the central edge DC current signal of the system into standard DC± 5V or 4-20mA output. It plays the role of monitoring and electrical isolation, and can be used with multi-loop monitoring instruments or other electrical measuring instruments.   


© 2025 安科瑞電氣股份有限公司 版權(quán)所有
滬ICP備05031232號-15 GoogleSiteMap 技術(shù)支持:制藥網(wǎng)    管理登陸    總訪問量:515843
12末发育娇小性色xxxx| 久久精品国产香蕉亚洲AV| 嫩草伊人久久精品少妇av网站| 人人妻人人澡人人爽曰本| 高清破外女出血视频全过程| 肉大捧一进一出免费视频| 免费无码一区二区三区蜜桃大 | 国产亚洲精久久久久久无码蜜桃 | 亚洲熟伦熟女专区| 99热这里有精品| 四虎成人精品国产永久免费无码| 按摩男让我高潮做了3次正常吗 | h双腿涨灌捆绑play慎入| 在床边趴着屁股撅起来怎么弄| 国产高潮国产高潮久久久| 国产精品一区久久久久久| 亚洲精品无码成人| chinese山西老熟女bbw| 中学生广播体操舞动青春| 人人妻人人澡人人爽人人DVD| 无遮挡又黄又刺激的视频 | 无码AV免费毛片一区二区| 国产真人无码作爱免费视频APP| 10后学生小嫩嫩xxx| 岳今晚让我玩个够肥水一体探岳体| 好色先生tv| 国产精品久久久久久久久久免费| 中文字幕在线精品视频入口一区| 日日狠狠久久8888偷偷色| 嗯h客厅h禁欲教授| 第一次啪要猛j还是要温柔点| 40熟妇疯狂做受xxxx高潮| 野外玩弄大乳孕妇| 高h猛烈失禁潮喷a片在线观看| 国产免费一区二区三区免费视频| 中文字幕AV人妻一区二区| 国内少妇人妻偷人精品xxx| 男女无遮挡xx00动态图120秒| 门卫老李干了校花高小柔| 国产特黄级aaaaa片免| 色欲AV蜜臀一区二区三区|